DCPR 2034 Fire Doors: Mumbai's Own Rulebook

Mumbai is the one city in Maharashtra UDCPR does not govern. The Mumbai Fire Brigade writes against DCPR 2034, names one-hour duplex and lift doors and two-hour DG set doors, and specifies the terrace refuge door down to a 6 inch breakable glass port.

VValtrix Engineering TeamValtrix Fire Safety Solutions13 Nov 20268 min read
DCPR 2034 Fire Doors: Mumbai's Own Rulebook

Mumbai is the one city in Maharashtra that UDCPR does not govern. Buildings inside MCGM limits are regulated by DCPR 2034, and the Mumbai Fire Brigade writes its fire safety requirements against that rulebook. A door schedule carrying UDCPR clause numbers does not transfer.

This matters because specifications get copied. A schedule written for a Pune or Nashik tower looks correct, cites real regulations, and is still pointing at the wrong document once the project is in Mumbai.

What changes and what does not

Changes: the development control regulation. DCPR 2034 in Mumbai, UDCPR in the rest of the state, each with its own clause numbering and its own tests.

Does not change: the Maharashtra Fire Prevention and Life Safety Measures Act, 2006, the National Building Code, and IS 3614:2021, which is what the doorset itself is certified to.

Two rulebooks, one state

The Unified Development Control and Promotion Regulations were sanctioned to bring most of Maharashtra under one set of building rules. Mumbai was kept out. The Municipal Corporation of Greater Mumbai area runs on the Development Control and Promotion Regulations 2034.

You can see it in the Fire Brigade's own documents rather than having to take anyone's word for it. MCGM's codified fire safety requirements specify staircase layout and flight width "as per Regulation 37(15) & 47 of DCPR- 2034", and require corridor and lift lobby ventilation "as per the provisions of DCPR-2034".

So the practical test is jurisdiction, not geography-by-feel. Inside MCGM limits it is DCPR 2034 and the Mumbai Fire Brigade. Outside, in most of the state, it is UDCPR and the local corporation or MIDC, and the UDCPR special building test applies instead.

The door ratings Mumbai Fire Brigade puts in writing

MCGM publishes codified requirements by building category. Everything quoted in this section comes from the set for low-rise residential buildings up to 32 m. Taller buildings and other occupancies have their own documents, so confirm which category your project sits in before ordering anything against these figures.

Duplex flat entrance doors: one hour

"Entrance/Exit doors of the Upper duplex rooms is having Fire rating not less than one hrs." The same clause requires those doors to open into the protected common lift lobby or corridor passage "without any hindrances", and a second clause requires them not to be obstructed at any time.

One hour is an FD60 doorset. The "without hindrance" wording is about the swing and the route, which is a design decision, not something to fix on site later.

Lift doors: one hour, and solid

"Collapsible gates shall not be permitted for lifts; the lifts shall have solid doors with fire resistance of at least one hour." This one is unambiguous and it rules a product out rather than just setting a number.

DG set room: two hours

"The door of DG Set room is 2 hrs. fire resistance." That is an FD120 doorset. It sits consistently with how NBC 2016 Part 4 treats plant rooms, where substation and switch room openings are rated 120 min and a boiler room entry door is a composite door of 120 min.

Car parking: two hours on structure and decks

"Elements of the car parking structure are 2 hr. fire resistance" and "Each car parking deck is 2 hr. fire resistance". Where an opening passes into those decks, that is the rating the compartment is being held to.

Fire door hardware installation, the detail a Mumbai Fire Brigade occupation NOC inspection checks
MFB checks the doorset as installed at occupation stage, with a checklist signed by the architect or licensed surveyor.

The terrace door is a refuge door

This is the requirement most schedules miss entirely, because it is not a rating. Mumbai treats the terrace floor as a refuge area: "Terrace floor of the building shall be treated as Refuge Area."

The door onto it carries three specific features:

  • Louvers. "The top half portion of the doors provided with louvers." The access doors from the enclosed staircase to the terrace carry the same requirement.
  • Latch on the terrace side. "The latch-lock installed from the terrace side at the height if not more than 1 mtrs."
  • A breakable glass port. "The glass front of 6 inch diameter with the breakable glass is provided just above the latch lock, so as to open the latch in case of an emergency by breaking glass."

On top of that, the terrace entrance doors are "painted or fixed with sign painted in luminous paint mentioning REFUGE AREA".

Read that as a manufacturing instruction, because that is what it is. A louver, a glazed port and a particular latch position are part of the doorset, and they have to be inside the tested assembly. Cutting a louver or a glass port into a certified leaf after delivery changes the assembly and voids the evidence it was certified on, which is the failure described in how to verify a fire door is really certified. The only way this works is to put it in the enquiry.

What a copied schedule gets wrong

When a specification travels from another Maharashtra city into Mumbai, these are the things that break:

  • Clause references. A UDCPR regulation number means nothing to an MFB officer reviewing the proposal.
  • The classification test. UDCPR's special building definition, which turns on 500 sq.m. on any floor irrespective of height, is not how a Mumbai building gets classified.
  • The terrace door. Specified as a plain rated leaf almost everywhere else, and specified in detail here.
  • Lift openings. A collapsible gate that passes elsewhere is explicitly not permitted.
  • The approval sequence. MFB stipulates requirements at plan stage, then runs a separate occupation NOC checklist signed by the architect or licensed surveyor. Its letters note that additional requirements recommended before final occupation must also be complied with, so the plan-stage list is a floor rather than a ceiling.

What survives the move intact is the doorset evidence itself. IS 3614:2021 certification does not change at a municipal boundary, and neither does Section 3(3) of the Maharashtra Fire Prevention and Life Safety Measures Act, 2006, which requires a maintenance certificate from a licensed agency twice a year, in January and July.

A short Mumbai check before you order

  • Confirm the jurisdiction. Inside MCGM limits, DCPR 2034 and MFB. Outside, a different rulebook and a different authority.
  • Confirm the building category. The codified requirements quoted here are the low-rise residential set, up to 32 m. Get the right document for your project.
  • List the terrace and refuge doors separately in the enquiry, with louver, latch height, glass port and signage called out.
  • Check the lift openings are solid doors rated at least one hour, not gates.
  • Check the plant rooms. DG set room at two hours; car parking decks and structure at two hours.
  • Ask for the test evidence that covers each configuration you are actually buying, including any leaf with a louver or vision panel in it.

More detail on the local picture is on our fire doors in Mumbai page, and for the rating logic across a whole building, NBC 2016 fire door requirements for high-rise.

Frequently asked questions

Does UDCPR apply in Mumbai?

No. Buildings inside MCGM limits are governed by DCPR 2034. The Mumbai Fire Brigade's codified requirements cite Regulation 37(15) and 47 of DCPR-2034 for staircases and refer to DCPR-2034 for corridor and lift lobby ventilation. The Maharashtra Fire Prevention and Life Safety Measures Act, 2006 does apply statewide, Mumbai included.

What fire rating does a duplex flat door need in Mumbai?

MCGM's codified requirements for low-rise residential buildings up to 32 m state that entrance and exit doors of upper duplex rooms have a fire rating of not less than one hour, and open into the protected common lift lobby or corridor without hindrance. One hour is an FD60 doorset.

Are collapsible lift gates allowed in Mumbai buildings?

No. The codified requirements state that collapsible gates shall not be permitted for lifts, and that lifts shall have solid doors with fire resistance of at least one hour.

Why does a terrace door need a breakable glass panel?

Because the terrace is a refuge area and people must be able to reach it in an emergency. The requirement is a 6 inch breakable glass port just above a latch-lock fitted on the terrace side at not more than 1 m height, so the latch can be opened by breaking the glass. The top half of the door also carries louvers.

Can a louver or vision panel be cut into a certified fire door on site?

No. The certification covers a tested configuration. Adding a louver, glazed port or vision panel after manufacture changes that assembly and the test evidence no longer describes the door that is installed. Specify these features at enquiry stage so the doorset is built and certified with them.

Is the fire NOC a one-time approval in Mumbai?

The approval itself is staged, with requirements set at plan stage and a separate occupation NOC before the occupancy certificate. Beyond that, Section 3(3) of the Maharashtra Fire Prevention and Life Safety Measures Act, 2006 requires a maintenance certificate in the prescribed form twice a year, in January and July, confirming the measures remain in good repair and efficient condition.


Sources: the Mumbai Fire Brigade's codified fire safety requirements for low-rise residential buildings up to 32 m, published on the MCGM portal; DCPR 2034; the Maharashtra Fire Prevention and Life Safety Measures Act, 2006; and the National Building Code of India 2016 Part 4, published by BIS. Requirements differ by building category and change over time, so confirm the current set with MCGM for your project.

Valtrix manufactures IS 3614:2021 certified fire doorsets from FD30 to FD180 at Dhakambe, Dindori, Nashik, and supplies projects across Maharashtra. See the full doorset range, the industries we supply, or our Mumbai page.